@article{oai:sangitan.repo.nii.ac.jp:00000013, author = {畑迫, 健一}, issue = {1}, journal = {産業技術短期大学誌, BULLETIN OF COLLEGE OF INDUSTRIAL TECHNOLOGY}, month = {Mar}, note = {A parallel operation experiment was conducted with two synchronous generators. In parallel operation, a cross current flows between the two generators due to the phase difference of the induced electromotive force, and this cross current causes the active power to lag behind the generator whose phase is advanced. A generator whose phase is delayed reduces active power and advances the phase. Furthermore, it was found that if the magnitude of the induced electromotive force is different during parallel operation, a cross current flows between the two generators, and the reactive power is given from the generator with the large electromotive force to the generator with the small electromotive force. This reactive current reduces the difference in electromotive force between generators. It was confirmed that the exchange of active power and reactive power works to maintain parallel operation.}, pages = {11--16}, title = {03_同期発電機の並行運転時の有効電力・無効電力の解析}, volume = {55}, year = {2022}, yomi = {ハタサコ, ケンイチ} }